Overview

High Yield

High Yield

· 12/6 MPPTs design with maxefficiency 99.02%, 12 MPPT design,compatible with bifacial PV panel

· Up to 20A max current per PVstring, compatible with large current/bifacial modules

Safe and reliable

Safe and reliable

· IP66 and optional C5 anti-corrosiongrade, intelligent fan with IP68protection

· Integrated DC&AC SPD

Easy O&M

Easy O&M

· Optional intelligent I-V and fault waverecording, quick failure analysis

· Key components life optimizationdesign Reduce failure risk

System optimization

· Optional PLC communication, savecommunication cable investment

· Optional Q at night function QuickDynamic response

Technical Specification

Items SPI250K-B-HX2 SPI250K-B-H X2P
DC Input(PV)
Max. PV input voltage 1500Vdc
Rated input voltage 1080Vdc
Max. current per MPPT 30A 60A
No.of MPPTs 12 6
No.of PV strings per MPPT 2 3
MPPT voltage range 500~1500Vdc
Starting voltage 550Vdc
DC switch Yes
AC Output (On-grid)
Rated AC output power 250kW@30℃,225kW@40℃,200kW@50℃
Max. output power 250kVA
Rated AC output voltage 800Vac
Rated output current 180.4A
Max. output current 180.4A
Rated grid frequency 50Hz/60Hz
Grid frequency range 45-55Hz/55-65Hz
Power factor >0.99(rated power)
Adjustable power factor 0.8(leading)-0.8(lagging)
THDi <3%(rated power)
Efficiency*
Max. eficiency 99.02%
European efficiency 98.80%
MPPTefficiency 99.90%
Function and protection
Anti-islanding Yes
DC(PV)reversed connection Yes
AC short circuit protection Yes
Temperature protection Yes
Surge protection DC Type ll&AC Type ll
AFCI function Yes (optional)
Integrated PID function Yes (optional)
IV curve scan and diagnosis Yes (optional)
Support night SVG function Yes (optional)
General
Dimensions(W*H’D) 1100*760*361mm
Weight 117kg
Pgrade IP66
Self-consumption at night <2W
Cooling type Intelligent forced air cooling
Altitude 4000m(>3000m derating)
Operating temperature -35~60℃
Relative humidity 0~100%
Display LED+APP
DC terminal MC4 Terminal
AC terminal OT Terminal
Installation method Wall-mounted
Communication RS485,PLC(optional),WIFI (optional)/4G(optional)
Compliance EN 62109-1/2,IEC62109-1/2,ENIEC 61000-6-2/4.
IEC62116,IEC61727,CEI 0-16,EN 50549-2,NC RfG
·”Data under laboratory test conditions.
· Specifications are subject to change without prior notice.

 

PV Power Plant Application

37MW-String-Inverter-PV-Project-in-Poland

37MW String Inverter PV Project in Poland

260MW Central Inverter PV Project in China

260MW Central Inverter PV Project in China

30-MW-Central-PV-Project-in-Argentina

30 MW Central PV Project in Argentina

2-MW-PV-Project-in-Poland-1

2 MW PV Project in Poland

Renewable Energy / Utility PV

20 MW Solar Power Plant in Latin America

20 MW Solar Power Plant in Latin America

2GW+ Large-scale Ground PV Project in Rajasthan, India

2GW+ Large-scale Ground PV Project in Rajasthan, India

115 MW PV Power Plant in Europe

115 MW PV Power Plant in Europe

9.9MW PV Power Plant Project in Croatia

9.9MW PV Power Plant Project in Croatia

Renewable Energy / C&I PV

1.5MW Roof Distributed PV Power Station Project in Poland

1MW Rooftop PV Project in Thailand

1MW Rooftop PV Project in Thailand

Rooftop PV Project in Europe

Rooftop PV Project in Europe

Rooftop PV Project in Europe

1MW PV Project in Bulgaria

Renewable Energy / Residential PV

Residential PV System in Poland

Residential PV System in Poland

Residential PV System in Pakistan

Residential PV System in Pakistan

Residential PV System in Brazil

Residential PV System in Brazil

Residential PV System in Brazil

Residential PV System in Brazil

Download

  • SPI250K-B-H X2/X2P

    Three-phase On-grid String Inverter

Contact our team

Do You Have A Query,
But Do Not Know who To Contact?